Operational Test
Activate the FXM self-test function.1.
After passing the self-test, disconnect the AC input to the FXM to 2.
trigger the FXM into the backup (inverter) mode.
Let the FXM operate in the backup mode for approximately 10 3.
minutes.
Measure the individual battery voltages while the FXM is operat-4.
ing in the backup mode. There should be no more than 0.6 volts
difference between the highest battery voltage and the lowest
battery voltage.
Caution
One battery measuring 2 volts lower than the other 3 batteries in the
string indicates a shorted cell in that battery. Replace all 4 batteries.
Three batteries in the string measuring the same voltage and one
battery measuring several volts higher indicates an open cell in the
battery with the higher reading. Replace all 4 batteries.
Verify that there is no Low Battery Alarm.5.
Reconnect the AC input.6.
Service and Technical Support
Alpha Technologies is committed to the support of Alpha products
throughout their life. Alpha provides a full range of service products
including extended warranties, on-site service plans and battery
renewal programs. Parts, supplies and replacement or upgraded
battery packs are also available. To discuss any of your after-sales
needs, please call 1-800-667-8743 and ask for Service.
86
FXM UPS Operator's Manual
Doc# 017-201-B0 Rev 0408
Page view 85
1 2 ... 81 82 83 84 85 86 87 88 89 90 91 ... 97 98

Comments to this Manuals

No comments