Page view 35
Logo Screen
(Figure 7.1)
System Status Menu
(Figure 7.5)
Control Menu
(Figure 7.4)
Alarm and Fault
Menus (If Active)
(
Figures 9.1 and 9.2)
Event Status Menu
(Page 43)
CANCEL
SCROLL
SELECT
SCROLL
SCROLL
CANCEL
SELECT
SCROLL
Starting at the Logo
Screen, press the SELECT
button to go down one level.
Press the SCROLL button to move between the menus. The
SCROLL button moves only in one direction, so if you overshoot, you
have to go all the way around the menu tree again.
Press the SELECT button to enter the submenu. Then press
the SCROLL button to cycle through the submenu items. The
SCROLL button moves only in one direction, so if you overshoot, you
have to go all the way around the submenu again.
The CONTROL MENU
(Figure 7.4) lets you
control, program and
adjust the FXM for
connection to trafc
intersection equipment
or other applications. You
can control the:
INVERTER
INV BYPASS
BATT TEST
AUTO TEST
SHUTDOWN
SENSE TYPE
FUNC MODE
VOLTAGE
FREQUENCY
QUAL TIME
BATT COMP
DATE SEL
INV RECORD
CHARGE CUR
The SYSTEM STATUS
menu (Figure 7.5) lets
you measure various
inputs, outputs and other
values. The available
measurements are:
VIN
VOUT
IOUT AC
BATT TEMP
FREQ IN
OUTPUT PWR
BATT VOLT
CHGR CUR
DATE
TIME
INV COUNT
INV TIMER
SHED TIMER 1, 2 OR 3
VERSION
The ALARM and FAULT
menus (Figures 9.1 and
9.2) are invisible and
disabled until the FXM has
a malfunction.
When the front panel’s
alarm LED is on or
ashing, press SELECT.
One of the malfunctions
listed in Figures 9.1 and
9.2 will appear on the LCD.
Press the SCROLL button
to see if more than one
malfunction is present.
Fix the malfunction. Press
the SELECT button to clear
the malfunction from the
screen.
If the malfunction is xed,
the malfunction is cleared
from the LCD. If it isn’t
xed, it will reappear on
the screen.
The EVENT STATUS menu
(See page 43) displays the
last 25 FXM events on the
LCD. For the 100-event log,
see page 54.
Press the SELECT button
to access the menu. Press
the SELECT then the
SCROLL button to scroll
through the events. To see
what a specic event was,
press the SELECT button.
Press the SCROLL button
to see what malfunction
triggered the event.
Figure 7. 3 - LCD Menu Tree