Wiring the External Batteries
WARNING
The batteries must be installed by qualified personnel trained in the
safe use of high-energy power supplies and their batteries.. Refer to
Product Safety Information on page 5.
Notes:
Use new batteries when installing a new unit. Verify they are all 1.
the same battery type with identical date codes.
For the FXM 650-24, the battery string is 24VDC. For the FXM 2.
650-48/1100/2000, the battery string is 48VDC.
If you are making your own battery 3. wiring harness, use at least 10
AWG (for FXM 650/1100) or 8 AWG (FXM 2000).
The battery return connection is to be treated as an Isolated DC 4.
return (DC-I) as defined in GR-1089-CORE.
Procedure
For FXM 650-48/1100/2000 (48 V battery string), number the 1.
batteries from 1 to 4 with labels or tape. For FXM 650-24 (24 V
battery string), number the batteries from 1 to 2. See Figure 3 .11.
Battery #4 Battery #3 Battery #2 Battery #1
To Positive
Terminal
To Negative
Terminal
Optional in-line fuse
Tape the battery temperature sensor to the side of either battery #2 or #3.
Battery #2 Battery #1
To Positive
Terminal
To Negative
Terminal
Optional in-line fuse
Tape the battery temperature sensor to the side of either battery #2 or #1.
Figure 3.11- External Battery Wiring (for 48VDC string (top) and 24VDC string)