6.9 Standard Control Logic,
continued
6.9.2 Float and Equalize Chart
Values given for 36V systems calculated at 77
o
F (25
o
C)
Example:
If a particular battery manufacturer calls for a FLOAT of 40.5 volts and EQUALIZE
of 41.4 volts, the board's FLOAT jumper is set to FLOAT "2" (40.5 volts). The board's
EQUALIZE jumper is set to EQU "1" (0.9 volts). This results in a FLOAT charge of 40.5
volts with an EQUALIZE charge of 41.4 volts (40.5 volts + 0.9 volts = 41.4 volts).
FLOAT EQUALIZE
Alpha Technologies does not assume responsibility for batteries damaged by
improper jumper settings. Always consult the battery manufacturer for correct charging
levels. If batteries appear to be over or under-charged, first check for defective batteries
and then verify the correct charge voltage settings.
6. INSTALLATION
30
Main Circuit Module Assembly (top view)
with APM Logic Upgrade
S402 S401
S401
S402
APM LOGIC UPGRADE
S402 (TEST)
60 Hz 50 Hz
1. 6.1 7.3
2. 12 14.5
3. 24 29
4. 48 57.6
60 Hz 50 Hz
5. 4.3 5.2
6. 8.5 10.2
7. 17 20.4
8. AOEQ AOEQ
INTERVAL
(in days)
DURATION
(in minutes)
S401 (EQU)
60 Hz 50 Hz
1. 3 3.6
2. 6 7.3
3. 12 14.5
4. 24 29
60 Hz 50 Hz
5. 17 20.4
6. 34 40.8
7. 1.2 H 1.4 H
8. 2.3 H 2.8 H
INTERVAL
(in days)
DURATION
(in minutes / hours)
Jumper 24V 36V 48V VDC Jumper 24V 36V 48V VDC
position Batt Batt Batt per cell position Batt Batt Batt per cell
Default 26.0 39.0 52.0 2.167 Default 0.0 0.0 0.0 0.000
FLOAT 1 26.4 39.6 52.8 2.200 EQ 1 0.6 0.9 1.2 0.050
FLOAT 2 27.0 40.5 54.0 2.250 EQ 2 1.2 1.8 2.4 0.100
FLOAT 3 27.6 41.4 55.2 2.300 EQ 3 1.8 2.7 3.6 0.150
00123123
FLOAT
EQU
Jumpers JP1