2. FRONT PANEL
11
2.5 Standby Data Display (SDD)
The optional, dual-function LED "STANDBY DATA" display is used to keep track of
accumulated inverter run time, and to record the number of standby events that have
occurred. The "ELAPSED TIME" clock is activated only when the power supply is in
inverter mode. Elapsed time will continue to accumulate until the clock is reset. The
"STANDBY EVENTS" counter displays the number of standby events that have lasted
longer than 60 seconds duration. Standby events will continue to accumulate until the
counter is reset. The SDD is equipped with an on-board battery to maintain data even
when the main circuit module is completely removed or a complete power outage (including
low battery shutdown) occurs .
2.5.1 "MODE" Switch
The "MODE" switch activates the display and verifies the mode of operation. When
the switch is pressed, the "ELAPSED TIME" LED will light (or "STANDBY EVENTS" LED
depending upon the mode). At the same time, the corresponding information will appear in
the "TIME/EVENTS" window for approximately 10 seconds. The next mode is activated
by pressing the switch again. "ELAPSED TIME" and "STANDBY EVENT" information can
be toggled by briefly pressing the "MODE" switch.
NOTE: To clear either the "ELAPSED TIME" or "STANDBY EVENT" memory, select
the desired mode. Press and hold the "MODE" switch until the LED flashes. Then, press
the MODE switch twice (in rapid succession). A single decimal point will appear in the
display when the memory has been cleared.
2.5.2 "ELAPSED TIME" LED
The "ELAPSED TIME" LED indicates the mode as the "TIME/EVENTS" window
displays the time accumulated during inverter operation. The clock, which displays time to
the nearest 0.1 hours, will continue to accumulate time until the memory is manually
cleared.
2.5.3 "STANDBY EVENTS" LED
The "STANDBY EVENTS" LED indicates the mode as the "TIME/EVENTS" window
displays standby events that have lasted more than 60 seconds in duration. The counter
will continue to register standby events until the memory is manually cleared.
2.5.4 "TIME/EVENTS" Window
The "TIME/EVENTS" window displays "ELAPSED TIME" in 0.1 hr increments, up to
999.9. "STANDBY EVENTS" are displayed in increments of 1, up to 9999.
"MODE" Switch
(Selects TIME or EVENTS mode; clears memory)
"ELAPSED TIME" (green) LED
(Indicates ELAPSED TIME mode)
"STANDBY EVENTS" (green) LED
(Indicates STANDBY EVENTS mode)
"TIME/EVENTS" Window
(Displays TIME and EVENTS information)
(OPTIONAL FEATURE)
STANDBY DATA Display
Page view 19
1 2 ... 15 16 17 18 19 20 21 22 23 24 25 ... 60 61

Comments to this Manuals

No comments