6.9 Standard Control Logic
The Main Circuit Module assembly comes equipped with circuitry to monitor incoming
AC, charge the batteries and control the inverter. The XM Series power module uses a
dual-mode (float and equalize) temperature compensated battery charger to maintain
the batteries. A Remote Temperature Sensor (RTS) plugs directly into the side of the
module (the other end is attached to the side of the center battery in the battery compart-
ment) to provide optimum temperature measurements. Battery charging voltages are
factory set and do not need to be reset unless the module assembly has been repaired or
has been tampered with, or when batteries (other than gelled-electrolyte) are being used.
NOTE: Always verify the battery charger switch settings before placing the unit into
service. The power module can be manually sequenced through its two charging modes
by pressing the front panel "CHARGE MODE" switch. The XM's front panel "CHARGER
STATUS" display indicates the charging mode.
6.9.1 Selecting Battery Charge Voltages
Always refer to the battery manufacturers specifications before selecting float and
equalize charge settings. Failure to do so could damage the batteries.
Procedure:
1. Remove the Main Circuit Module assembly from the left side of the power module.
2. Select the required float charge voltage by positioning the FLOAT jumper at JP1
located midway along the lower side of the main board (see illustration on below).
The jumper is factory set at FLOAT 2 (40.5V) for a 36 Volt battery string and can be
repositioned if necessary. Each position (FLOAT 1, 2, 3) provides a different voltage
(refer to the chart on the next page for 24 VDC, 36 VDC and 48 VDC applications). If
the jumper is removed, the float voltage will default to its 39.0 volt calibration level.
3. Select the required equalize charge voltage by positioning the EQU jumper located at
JP1 on the main board. The EQUALIZE jumper
adds 0.9V per setting above the
value of the FLOAT setting. The jumper is factory set at EQU 1 (0.9V) and can be
repositioned if necessary. Each position (EQU 1, 2, 3) will provide a different equalize
voltage (refer to the chart on the next page for 24 VDC, 36 VDC and 48 VDC applica-
tions). If the jumper is removed, the equalize voltage will default to 0.0 volts (39.0 volt
float calibration level).
4. If the unit is equipped with APM or USM logic upgrades, set the "Auto-Equalize"
and "Auto-Test" switches (section 6.10) before reseating the Main Circuit Module
assembly.
Main Circuit Module Assembly
29
6. INSTALLATION
J2
J4
J3
0 0 1 2 3 1 2 3
FLOAT
JP1
EQU
External Jack for RTS (Remote Temperature Sensor)
External Jack for Data
Logger
Edge Connector for APM logic
upgrade
(on back side of board)
Battery Charger Jumpers
(on component side of board)
Note: Float Positions "0 0" are
used for jumper storage only.
Optional APM and USM Plug-in Logic Upgrade