Alpha XM 6015 Series Operations Instructions Page 23

  • Download
  • Add to my manuals
  • Print
  • Page
    / 61
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 22
3.7 Battery Circuit Breaker
The 60 Amp battery circuit breaker is used to disconnect the batteries from the
module's DC circuit. With the breaker turned off, the power supply will not transfer to
standby mode. The inverter is disabled and the battery charger is unable to charge the
batteries. If a short circuit occurs in the DC circuitry, or battery polarity is accidently
reversed, the breaker will trip.
3.8 Main Circuit Module Assembly Access Handle
The main circuit module can be removed by firmly pulling the handle located on the
side of the unit. This facilitates easy access for logic upgrades, selection of float and
equalize charges and internal fuse replacements. The assembly can be removed during
LINE operation without interruption to the output. NOTE: See cautionary statements in
Section 6.8.
3.9 USM Connector Access
A cutout is provided in the Main Circuit Module Assembly to allow access to the board
connectors located on the USM logic upgrade. Status Monitoring communications and
tamper switch cables plug directly into the board's keyed connectors.
3.10 Remote Temperature Sensor Connector (RTS)
The Remote Temperature Sensor plugs directly into the "RJ-11C" type connector
located on the side panel. The sensor end of the RTS is routed into the battery compart-
ment and taped directly to the side of the center battery. This provides precise battery
temperature measurements in order to accurately adjust the battery charge voltage with
changes in battery temperature. If the remote temperature sensor is not connected, a
temperature sensor in the main circuit module adjusts the battery charge voltage with
changes in ambient temperature within the power supply.
3.11 Data Port
The Data Port is used in conjunction with optional hand-held DataLogger to retrieve and
store data directly from the power module during routine preventive maintenance. Caution:
No other devices should be plugged into the data port.