RESTORATION & MAINTENANCE
40
Alpha
®
Moisture Test Kit
STEP 1
Use Alpha
®
Ecogrinder (with dust carriage attached) to remove any foreign
objects and dust from the concrete surface to insure proper adhesion of the
sealant. Strictly follow guidelines given by Occupational Safety & Health
Administration (OSHA).
STEP 2
Weigh the container with the vinyl tape seal at the test location immediately
prior to initiating the test (W1).
Note: Be sure the scale is set to grams, ounce scales will not work for this
test. Weigh to the nearest 0.1 gram and note this initial weight on the top of
the container label using a felt tip pen or permanent marker as well as the
time and date the test was started (T1).
STEP 3
Remove the sealing tape from the plastic container. Make sure the tape
does not get dirty or lost since it will be needed to reseal the container at
the end of the test.
Note: For best results, stick the tape on the outer wall of the dome unit
to keep it safe.
STEP 4
Peel off the paper protective backing from the black sealant that is around the
dome and discard. Make sure the sealant material does not contact objects or
clothing as it is very sticky and intended to provide a secure, long-lasting seal to
the concrete throughout the duration of the test.
STEP 5 & 6
Carefully remove the lid from the container that holds the calcium
chloride crystals. Do not spill the crystals.
Install the test kit on the concrete oor. First, place the open calcium
chloride container on the concrete oor. Make sure the crystals are
relatively level. If any crystals are spilled the test can be invalid.
STEP 7
Next, immediately place the dome unit over the center of the dish. Press rmly along
the edges of the sealant material to securely bond the unit to the oor. To test for an
airtight seal, press rmly on the center of the cover. The cover should resist pressure,
if properly sealed.
Allow the test kit to remain undisturbed for a period of 60 to 72 hours. Note the ambient
temperature and humidity at the test area.
STEP 8
After 60 to 72 hours, remove the dome with a razor. Retrieve the dish with the cal-
cium chloride and immediately place the lid back on and reseal using saved vinyl
tape. Re-weigh the container on the same gram scale used at the
start of the test. Record weight, date and time (W2) (T2).
Note the weight as nal weight (W2). Do not spill any of the calcium
chloride crystals from the container. If any crystals are spilled, the
test must be rerun with a new test kit.
A person using this test kit shall strictly follow the instructions given in the latest
ASTM F 1869 published by American Society for Testing & Materials.
Step by Step Instructions